FPC 100 Automatic Pump Control
Electronics          Part numbers

FPC100 is a pump control unit designed to control and supervise submersible pumps. It operates the pump automatically without the use of level sensors. The moment the pump starts pumping air instead of liquid, it stops the pump cycle. It will then calculate the required "off-time" and automatically restart the pump at the appropriate time. Hence both pump wear and power consumption will be reduced significantly.

Features:
• Supervision functions

  • Stator winding temperature
  • Phase sequence for correct rotation
  • Phase asymmetry
  • Current from current transformer
  • Overvoltage and undervoltage

• High level switch can be used to trigger start
• Two relay outputs (PUMP and ALARM)
• Software controlled settings via a keypad

  • Relay functions
  • Start- and stop delays
  • Pause time adjustments
  • Parameter lock for unintentional change of set parameters

• Display indication

  • Total pumping time and number of pump starts
  • Pumping time after the latest start
  • Calculated time to start after the latest stop
  • Power and peak power in % of the measurement range
  • Supply voltage
  • Parameter settings
FPC 100

 

 


Electronics
Dimension (WHD) 45 90 115 mm (1.77" 3.54" 4.53")
Weight 0.3 kg (10.5 oz)
Supply voltage (VAC) 3 100–240, 3 x 380–500, 3 x 525–600, 3 x 600–690 (10 %), 3 600–690 not UL-recognized
Frequency 45–65 Hz
Current input Current transformers 10/0.055A, 25/0.055A, 50/0.055A or 100/0.055A. If current > 100 A a 10A transformer is used with an outer standard transformer
Power consumption Max 6 VA
Pump relay 5 A, 240 VAC resistive. 1.5 A 240 VAC pilot duty / AC12
Alarm relay 5 A, 240 VAC resistive. 1.5 A 240 VAC pilot duty / AC12
Fuse Max 10 A
Terminal wire size Use 75 C copper (Cu) wire only. 0.2–4 mm 2 single core, 0.2–2.5 mm 2 flexible core, stripped length 8 mm
Terminal tightening torque 5-7 lbs-in (0.56-0.79 Nm)
Repeatability power measurement 1 unit 24 h, 20 C
Temperature tolerance < 0.1 % / C
Operating temperature range –20 C to 50 C
Storage temperature range –30 C to 80 C
Protection class IP20
Compliance CE and cUL
DOT_CLEA.GIF (43 bytes)Part numbers
FPC100 including current transformer (CT)
Pump main voltage
(50/60Hz)
CT primary
rating (A)
Part number
3100–240V 10
25
50
100
652 02 01
652 02 02
652 02 03
652 02 04
3380–500V 10
25
50
100
652 02 05
652 02 06
652 02 07
652 02 08
3525–600V 10
25
50
100
652 02 09
652 02 10
652 02 11
652 02 12
3600–690V 10
25
50
100
652 02 13
652 02 14
652 02 15
652 02 16
DOT_CLEA.GIF (43 bytes)
FPC100 base unit
3100–240V 84 03 74
3380–500V 84 03 75
3525–600V 84 03 76
3600–690V 84 03 77
DOT_CLEA.GIF (43 bytes)
Current transformer (CT)
10A 83 95 85
25A 83 95 86
50A 83 95 87
100A 83 95 88